38
UMG 509
Cable type
The cable used must be suitable for an environmental
temperature of at least 80°C.
Recommended cable types:
Unitronic Li2YCY(TP) 2x2x0.22 (from Lapp Kabel)
Unitronic BUS L2/FIP 1x2x0.64 (from Lapp Kabel)
Maximum cable length
1200m at a baud rate of 38.4k.
Fig. Screening procedure at cabinet entry.
Cable
Strain relief
Screen braid of the cable
Earthing clamp
Noiseless ground
C
CAT cables are not suitable for bus wiring.
Use the recommended cable types for this.