39
UMG 509
Bus structure
• All devices are connected in a bus structure (line)
and each device has its own address within the bus
(see also Parameter programming).
• Up to 32 subscribers can be connected together
in a single segment.
• The cable is terminated with resistors (bus termination
120 Ohm, 1/4W) at the beginning and at the end
of a segment.
• With more than 32 subscribers, repeaters (amplifiers)
must be used to connect the individual segments.
• Devices for which the bus connection is switched
on must be under current.
• It is recommended that the master be placed
at the end of a segment.
• If the master is replaced with a bus connection,
the bus must be switched off.
• Replacing a slave with a bus connection that is either
switched on or de-energised can destabilise the bus.
• Devices that are not connected to the bus can
be replaced without destabilising the bus.
Fig. Bus structure
Slave
Slave
Slave
Slave
Slave
Slave
Repeater
Slave
Slave
Slave
Slave
Master
Speisung notwendig / power supply necessary
Busabschluß eingeschaltet / bus terminator on
T
T
T
T
T
Содержание UMG 509
Страница 15: ...15 UMG 509...
Страница 27: ...27 UMG 509...
Страница 101: ...101 UMG 509...
Страница 113: ...113 UMG 509...
Страница 117: ...117 UMG 509...
Страница 118: ...118 UMG 509 Dimension diagrams Cut out size 138 0 8 x 138 0 8 mm Rear side Patch cable...
Страница 119: ...119 UMG 509 Side view View from below...