67
UMG 509
Mode (absolute)
If a sampled value exceeds the set threshold value,
a transient is detected.
• Off
- Transient monitoring has been switched off.
• Automatic
- Factory default setting.
The threshold value is calculated automatically
and is 110% of the current 200 ms effective value.
• Manual
- The transient monitoring uses the
configurable threshold values under "Peak U".
Mode (delta)
If the difference between two neighbouring sampled
points exceeds the set threshold value, a transient
is detected.
• Off
- Transient monitoring has been switched off.
• Automatic
- Factory default setting. The threshold
value is calculated automatically and is 0.2175
times the current 200ms effective value.
• Manual
- The transient monitoring uses the
configurable threshold values under "Trns U".
Adopt L2-L4
The transient monitoring can be adjusted for each
phase. You can adopt these settings from phase L1 and
apply them to phases L2, L3 and L4.
• No
- The settings from phase L1 will not be applied
to phases L2, L3 and L4
• Yes
- The settings from phase L1 will be applied
to phases L2, L3 and L4