62
UMG 509
Voltage transformer
You can assign voltage transformer ratios to the baseline
measurement and the supporting measurement.
Select the 400 V / 400 V setting when measuring without
a voltage transformer.
Setting range:
Primary
1 to 999,999 V
Secondary
1 to 999 V
Factory default setting:
Primary
400
V
Secondary
400 V
Rated voltage
The rated voltage defines the value to which
• Transients,
• Events and the
• Automatic scaling of graphics relate.
Setting range:
0 to 1,000,000 V
Factory default setting:
Nominal voltage
230 V
You can also select the primary voltage as the nominal
voltage for example.
Содержание UMG 509
Страница 15: ...15 UMG 509...
Страница 27: ...27 UMG 509...
Страница 101: ...101 UMG 509...
Страница 113: ...113 UMG 509...
Страница 117: ...117 UMG 509...
Страница 118: ...118 UMG 509 Dimension diagrams Cut out size 138 0 8 x 138 0 8 mm Rear side Patch cable...
Страница 119: ...119 UMG 509 Side view View from below...