85
UMG 509
Voltage
and
current
have
a deviation of about 180°
in the phase position.
Phasor diagram, example 2
Predominantly ohmic load.
• The current measurement input is assigned
to the correct voltage measurement input.
• In the current measurement considered here,
the
k and l connections are reversed
or there is a
return feed in the mains power supply.
Voltage
and
current
only have
a minor deviation in the phase
length.
Phasor diagram, example 1
Predominantly ohmic load.
• The current measurement input is assigned
to the correct voltage measurement input.
Содержание UMG 509