107
UMG 509
Supply voltage
Installations of overvoltage category
III
Protection of the supply voltage (fuse)
6A, type C (approved i.a.w. UL/IEC)
230 V option:
- Nominal range
- Operating range
- Power consumption
95V to 240V (45-65Hz) or DC 80V .. 300V
+-10% of nominal range
max. 7W / 14VA
Terminal connection capacity (supply voltage)
Connectable conductors. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded
0.2 - 2.5mm
2
, AWG 24 - 12
Terminal pins, core end sheath
0.25 - 2.5mm
2
Tightening torque
0.5 - 0.6Nm
Stripping length
7mm
Current measurement
Rated current
5A
Resolution
0.1mA
Metering range
0.001 to 7 Arms
Measurement range exceeded (overload)
From 7 Arms
Crest factor
2.4
Overvoltage category
300V CAT III
Measurement surge voltage
4kV
Power consumption
approx. 0.2 VA (Ri=5mOhm)
Overload for 1 sec.
120A (sinusoidal)
Sampling rate
20kHz / phase