Positioning module UVE8112, IMD10 CanOpen
protocol
Manufacturer-specific parameters
Can Baud Rate
Ind
value
In the range of 2000
h
to 5FFF
h
of the object directory, there are those parameters that are not
predefined by a CanOpen specification.
ex Sub Name
Type
Attrib Map Default
Meaning
200
of the der CAN-Bus baud
rate in the modul
1
Can Baud Rate
RECORD
Displaying and changing
2001
N
3
Number of entries
00
Number of Entries
Unsigned 8
CONST
2001
01
Actual Baud Rate
Unsigned 8
RO
N
Current Baud Rate Code
200
bmode
Unsigned 8
RO
N
Current Baud Rate Code
High Speed Submode
1 02 Actual High Speed
Su
in
200
N
in
1 03 New High Speed Unsigned 8
RW
Submode
0
New Baud Rate Code
High Speed Submode
With a double click on the objet 2001-03 New High Speed Subm
he
accordant DIP switch have to be set (see Chapter DIP switch in
The following baud rate code is used in the object Can Baud Rate:
CAN-Bus Baud Rate
ode you can change the baud rate. T
Description of the drive module).
Baud Rate Code
0 1000
kBit/s
1
800 kBit/s (not supported)
2 500
kBit/s
3 250
kBit/s
4 125
kBit/s
5
Reserviert (not supported)
6 50
kBit/s
7 20
kBit/s
8
10 kBit/s (not supported)
Relation between Baud rate and wire length of CAN bus:
Baud Rate (kBit/s)
20 50 125
250
500
1000
Wire length (m)
2500 1000 500 250 100 25
Maximum jerk
Index Sub Name
Type
Attrib Map Default
value
Meaning
2040
00
Max. jerk
Unsigned 32
RW
N
10000000
Max. jerk in user-defined
unit / s³.
105
Содержание IMD1
Страница 1: ...DC servo positioning module with CanOpen interface UVE8112 IMD10 www isel com ...
Страница 66: ...DcSetup programme Positioning module UVE8112 IMD10 66 ...
Страница 113: ...Positioning module UVE8112 IMD10 Appendix 113 Appendix UVE8112 package dimensions ...
Страница 114: ...Appendix Positioning module UVE8112 IMD10 114 IMD10 package dimensions ...