Detailed Function Description
70
Please refer to description of AI1.
Notice: When AI2 is set as 0~20mA current input, the corresponding voltage range
is 0~5V.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.35
HDI1 function
selection
0~4 0
P5.36
HDI2 function
selection
0: Reference input
1: Counter input
2: Length input
3: Reserved
4: Reserved
0~4 0
0: Reference input, such as frequency, PID setting and PID feedback.
1: Counter input: Input of counter pulse.
2: Length input: Input of length pulse.
Notice: When P5.35 or P5.36 is set to be 0, P5.37~P5.46 will take effective
accordingly.
Function
Code
Name
Description
Setting Range
Factory
Setting
P5.37
HDI1 lower limit
0.0 kHz ~50.0kHz
0.0~50.0
0.0kHz
P5.38
HDI1 lower limit
corresponding
setting
-100.0%~100.0% -100.0~100.0
0.0%
P5.39
HDI1 upper limit
0.0 kHz ~50.0kHz
0.0~50.0
50.0kHz
P5.40
HDI1 upper limit
corresponding
setting
-100.0%~100.0% -100.0~100.0
100.0%
P5.41
HDI1 filter time
constant
0.00s~10.00s 0.00~10.00
0.10s
P5.42
HDI2 lower limit
0.0 kHz ~50.0kHz
0.0~50.0
0.0kHz
P5.43
HDI2 lower limit
corresponding
setting
-100.0%~100.0% -100.0~100.0
0.0%
P5.44
HDI2 upper limit
0.0 kHz ~50.0kHz
0.0~50.0
50.0kHz
P5.45
HDI2 upper limit
corresponding
setting
-100.0%~100.0% -100.0~100.0
100.0%
P5.46
HDI2 filter time
constant
0.00s~10.00s 0.00~10.00
0.10s
The description of P5.37~P5.46 is similar to AI1.
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...