List of Function Parameters
114
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P4.02
Torque boost
cut-off
0.0%~50.0% (motor rated
frequency)
20.0%
◎
BOOST
CUT-OFF
P4.03
V/F frequency 1
0.00Hz~ P4.05
5.00Hz
◎
V/F FREQ 1
P4.04
V/F voltage 1
0.0%~100.0%
10.0%
◎
V/F
VOLTAGE 1
P4.05
V/F frequency 2
P4.03~ P4.07
30.00Hz
◎
V/F FREQ 2
P4.06
V/F voltage 2
0.0%~100.0%
60.0%
◎
V/F
VOLTAGE 2
P4.07
V/F frequency 3
P4.05~ P2.01
50.00Hz
◎
V/F FREQ 3
P4.08
V/F voltage 3
0.0%~100.0%
100.0%
◎
V/F
VOLTAGE 3
P4.09
V/F slip
compensation
0.00~10.00Hz
0.0Hz
○
V/F SLIP
COMP
P4.10
AVR function
0: Disabled
1: Enabled all the time
2: Disabled during
deceleration
1
○
AVR
P4.11
Auto energy saving
selection
0: Disabled
1: Enabled
0
○
ENERGY
SAVING
P4.12
FWD/REV enable
option when power
on
0: Disabled
1: Enabled
0
○
FWD/REV
ENABLE
P5 Group: Input Terminals
P5.00
HDI selection
0: HDI1 and HDI2 are high
speed pulse input.
1: HDI1 is ON-OFF input,
HDI2 is high speed pulse
input.
2: HDI2 is ON-OFF input,
HDI1 is high speed pulse
input.
3: HDI1 and HDI2 are
ON-OFF input.
0
◎
HDI
SELECTION
P5.01
Input selection
0: Concrete
1: Virtual
0
◎
INPUT
SELECTION
P5.02
S1 Terminal
function
1
◎
S1
FUNCTION
P5.03
S2 Terminal
function
0:Invalid
1:Forward
2:Reverse
3:3-wire control
4:Jog forward
5:Jog reverse
6:Coast to stop
7:Reset fault
4
◎
S2
FUNCTION
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...