List of Function Parameters
128
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
PB.04
Overload
pre-warning
threshold
20.0%~150.0%
130.0%
○
OL WARN
CURR
PB.05
Overload
pre-warning
selection
0: Always detect relative to
motor rated current
1: Detect while constant
speed relative to motor rated
current
2: Always detect relative to
inverter rated current
3: Detect while constant
speed relative to inverter
rated current
0
◎
OL WARN
SELECT
PB.06
Overload
pre-warning delay
time
0.0~30.0s
5.0s
○
OL WARN
DELAY
Pb.07
Threshold of
trip-free
230.0V~600.0V
450.0V
○
TRIPFREE
POINT
PB.08
Decrease rate of
trip-free
0.00Hz~P0.07
0.00Hz
○
TRIPFREE
DECRATE
PB.09
Over-voltage stall
protection
0: Disabled
1: Enabled
0
○
OVER VOLT
STALL
PB.10
Over-voltage stall
protection point
120~150%
125%
○
OV PROTECT
POINT
PB.11
Over-current
protection
0: Disabled
1: Enabled
1
○
OVER CURR
PB.12
Over-current stall
threshold
100~200%
160%
○
OC
THRESHOLD
PB.13
Frequency
decrease rate
0.00~50.00Hz/s
1.00 Hz/s
○
FREQ DEC
RATE
PC Group: Serial Communication
PC.00
Local address
1~247
0: broadcast address
1
○
LOCAL
ADDRESS
PC.01
Baud rate selection
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
4
○
BAUD RATE
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...