Detailed Function Description
79
Function
Code
Name
Description
Setting
Range
Factory
Setting
P7.16
Output
frequency
at current
fault
Output frequency at current fault.
P7.17
Output
current at
current
fault
Output current at current fault.
P7.18
DC bus
voltage at
current
fault
DC bus voltage at current fault.
P7.19
Input
terminal
status at
current
fault
This value records ON-OFF input terminal
status at current fault. The meaning of each
bit is as below:
9
8
7
6
5
4
3
2
1
0
S8 S7 S6 HDI2 HDI1 S5 S4 S3 S2 S1
1 indicates corresponding input terminal is
ON, while 0 indicates OFF.
Notice: This
value is displayed as decimal.
P7.20
Output
terminal
status at
current
fault
This value records output terminal status at
current fault. The meaning of each bit is as
below:
BIT5
BIT4
BIT3
BIT2
BIT1
BIT0
RO3 RO2 RO1 HDO Y2 Y1
1 indicates corresponding output terminal is
ON, while 0 indicates OFF.
Notice: This
value is displayed as decimal.
6.9 P8 Group --Enhanced Function
Function
Code
Name
Description
Setting Range
Factory
Setting
P8.00
Acceleration time 1
0.0~3600.0s
0.0~3600.0
20.0s
P8.01
Deceleration time 1
0.0~3600.0s
0.0~3600.0
20.0s
P8.02
Acceleration time 2
0.0~3600.0s
0.0~3600.0
20.0s
P8.03
Deceleration time 2
0.0~3600.0s
0.0~3600.0
20.0s
P8.04
Acceleration time 3
0.0~3600.0s
0.0~3600.0
20.0s
P8.05
Deceleration time 3
0.0~3600.0s
0.0~3600.0
20.0s
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...