Detailed Function Description
46
Function
Code
Name
Description
Setting Range
Factory
Setting
P0.09
Lower frequency
limit
0.00Hz~ P0.08
0.00~P0.08
0.00Hz
Notice:
z
Lower frequency limit should not be greater than upper frequency limit
(P0.08).
z
If frequency reference is lower than P0.09, the action of inverter is
determined by P1.14. Please refer to description of P1.14.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P0.10
Keypad
reference
frequency
0.00 Hz ~ P0.08
0.00~P0.08
50.00Hz
When P0.03 is set to be 0, this parameter is the initial value of inverter reference
frequency.
Function
Code
Name
Description
Setting Range
Factory
Setting
P0.11
Acceleration time 0
0.0~3600.0s
0.0~3600.0
20.0s
P0.12
Deceleration time 0
0.0~3600.0s
0.0~3600.0
20.0s
Acceleration time is the time of accelerating from 0Hz to maximum frequency (P0.07).
Deceleration time is the time of decelerating from maximum frequency (P0.07) to 0Hz.
Please refer to following figure.
Figure 6.2 Acceleration and Deceleration time.
Содержание CHV Series