List of Function Parameters
112
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P2.01
Motor rated
frequency
0.01Hz~P0.07
50.00Hz
◎
MOTOR
RATE FREQ
P2.02
Motor rated speed 0~36000rpm
1460
rpm
◎
MOTOR
RATE SPEED
P2.03
Motor rated voltage 0~3000V
Depend
on model
◎
MOTOR
RATE VOLT
P2.04
Motor rated current 0.1~2000.0A
Depend
on model
◎
MOTOR
RATE CURR
P2.05
Motor rated power 1.5~900.0kW
Depend
on model
◎
MOTOR
RATE
POWER
P2.06
Motor stator
resistance
0.001~65.535
Ω
Depend
on model
○
STATOR
RESISTOR
P2.07
Motor rotor
resistance
0.001~65.535
Ω
Depend
on model
○
ROTOR
RESISTOR
P2.08
Motor leakage
inductance
0.1~6553.5mH
Depend
on model
○
LEAK
INDUCTOR
P2.09
Motor mutual
inductance
0.1~6553.5mH
Depend
on model
○
MUTUAL
INDUCTOR
P2.10
Current without
load
0.01~655.35A
Depend
on model
○
NO LOAD
CURR
P3 Group: Vector Control
P3.00
ASR proportional
gain K
p
1
0~100
20
○
ASR Kp1
P3.01
ASR integral time
K
i
1
0.01~10.00s
0.50s
○
ASR Ki1
P3.02
ASR switching
point 1
0.00Hz~P3.05
5.00Hz
○
ASR
SWITCHPOIN
T1
P3.03
ASR proportional
gain K
p
2
0~100
25
○
ASR Kp2
P3.04
ASR integral time
K
i
2
0.01~10.00s
1.00s
○
ASR Ki2
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...