3. DISASSEMBLE AND INSTALLATION
●
Any untrained person working on any parts/systems of inverter or any rule in the
“Warning” being violated, that will cause severe injury or property damage. Only
licensed person, who has been trained on design, installation, commissioning and
operation of inverter, is permitted to operate this equipment.
●
Input power cable must be connected tightly, and the equipment must be grounded
securely.
●
Even if the inverter is not in operating situation, the following terminals still have
dangerous voltage:
- Power Terminals: R, S, T
- Motor Connection Terminals: U, V, W.
●
Can not install the inverter until discharged completely after the power supply is
switched off for 5 minutes.
●
The section area of grounding conductor must be no less than that of power supply
cable.
●
Lift the cabinet by its base; do not lift it by holding its panel. Otherwise the main
unit will fall off to result in personal injury.
●
Install the inverter on top of the fireproofing material (such as, metal) to prevent
fire.
●
When need install two or more inverters in one cabinet, cooling fan should be
applied to make sure that the air temperature is lower than 45°C. Otherwise it
could cause fire or damage the device.
WARNING
CAUTION
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...