Detailed Function Description
72
Setting
Value
Function
Description
7
Frequency
reached
Please refer to description of P8.27.
8
Zero speed
running
ON: The running frequency of inverter is zero.
9
Preset count
value reached
Please refer to description of P8.22.
10
Specified count
value reached
Please refer to description of P8.23.
11
Length reached
ON: Actual length (P8.20) reach the value of P8.19.
12
PLC cycle
completed
After simple PLC completes one cycle, inverter will
output ON signal for 200ms.
13
Running time
reached
ON: The accumulated running time of inverter reaches
the value of P8.24.
14
Upper frequency
limit reached
ON: Running frequency reaches the value of P0.08.
15
Lower frequency
limit reached
ON: Running frequency reaches the value of P0.09.
16
Ready
ON: Inverter is ready (no fault, power is ON).
17
Auxiliary motor 1
started
18
Auxiliary motor 2
started
In the case of simple water supply system with one
inverter driving three pumps, it is used to control
auxiliary pumps. For details, please refer to
descriptions of P8.29, P8.30 and P8.31.
19
Motor running
ON: Inverter has output signal
20
Stop pulse
output
Output pulse signal for 2s when running frequency is
lower than 0.1Hz
21~31 Reserved Reserved
Function
Code
Name
Description
Setting
Range
Factory
Setting
P6.07
AO1 function selection
Multifunctional analog
output
0~14 0
P6.08
AO2 function selection
Multifunctional analog
output
0~14 0
P6.09
HDO function selection
Multifunctional
high-speed pulse
output
0~14 0
AO/HDO output functions are indicated in the following table:
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...