Detailed Function Description
52
Figure 6.5 S curve diagram.
Function
Code
Name
Description
Setting Range
Factory
Setting
P1.08 Stop
Mode
0:Deceleration to stop
1:Coast to stop
0~1 0
0: Deceleration to stop
When the stop command takes effect, the inverter decreases the output frequency
according to P1.05 and the selected acceleration/deceleration time till stop.
1: Coast to stop
When the stop command takes effect, the inverter blocks the output immediately. The
motor coasts to stop by its mechanical inertia.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P1.09
Starting frequency of DC
braking
0.00~P0.07 0.00~10.00
0.00Hz
P1.10
Waiting time before DC
braking
0.0~50.0s 0.0~50.0 0.0s
P1.11
DC braking current
0.0~150.0%
0.0~150.0
0.0%
P1.12
DC braking time
0.0~50.0s
0.0~50.0
0.0s
Starting frequency of DC braking: Start the DC braking when running frequency reaches
starting frequency determined by P1.09.
Waiting time before DC braking: Inverter blocks the output before starting the DC braking.
After this waiting time, the DC braking will be started. It is used to prevent over-current
fault caused by DC braking at high speed.
DC braking current: The value of P1.11 is the percentage of rated current of inverter. The
bigger the DC braking current, the greater the braking torque.
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...