Detailed Function Description
67
K1 K2 Run
command
OFF OFF
Stop
ON OFF
FWD
OFF ON
REV
ON ON
Stop
Figure 6.13 2-wire control mode 1.
1: 2-wire control mode 2: START/STOP command is determined by FWD terminal. Run
direction is determined by REV terminal.
Figure 6.14 2-wire control mode 2.
2: 3-wire control mode 1: SB1: Start button. SB2: Stop button (NC), K: Run direction
button, Terminal SIn is the multifunctional input terminal of S1~S8, HDI1 and HDI2. The
terminal function should be set to be 3 (3-wire control).
Figure 6.15 3-wire control mode 1.
3: 3-wire control mode 2:
SB1: Forward run button
SB2: Stop button (NC)
SB3: Reverse run button
Terminal SIn is the multifunctional input terminal of S1~S8, HDI1 and HDI2. The terminal
function should be set to be 3 (3-wire control).
K1 K2
Run
command
OFF OFF
Stop
ON OFF
FWD
OFF ON
Stop
ON ON
REV
K Run
command
OFF FWD
ON REV
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...