Detailed Function Description
94
Function
Code
Name
Description
Setting Range
Factory
Setting
PA.26
Multi-step speed 12
-100.0~100.0%
-100.0~100.0
0.0%
PA.27 12
th
Step running time
0.0~6553.5s(h)
0.0~6553.5
0.0s
PA.28
Multi-step speed 13
-100.0~100.0%
-100.0~100.0
0.0%
PA.29 13
th
Step running time
0.0~6553.5s(h)
0.0~6553.5
0.0s
PA.30
Multi-step speed 14
-100.0~100.0%
-100.0~100.0
0.0%
PA.31 14
th
Step running time
0.0~6553.5s(h)
0.0~6553.5
0.0s
PA.32
Multi-step speed 15
-100.0~100.0%
-100.0~100.0
0.0%
PA.33 15
th
Step running time
0.0~6553.5s(h)
0.0~6553.5
0.0s
Notice:
z
100% of multi-step speed x corresponds to the maximum frequency (P0.07).
z
If the value of multi-step speed x is negative, the direction of this step will be
reverse, otherwise it will be forward.
z
The unit of x step running time is determined by PA.36.
Selection of step is determined by combination of multi-step terminals. Please refer to
following figure and table.
Figure 6.34 Multi-steps speed operation diagram.