List of Function Parameters
116
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P5.17
AI1 upper limit
0.00V~10.00V
10.00V
○
AI1 UP LIMIT
P5.18
AI1 upper limit
corresponding
setting
-100.0%~100.0%
100.0%
○
AI1 UP
SETTING
P5.19
AI1 filter time
constant
0.00s~10.00s
0.10s
○
AI1 FILTER
TIME
P5.20
AI2 lower limit
0.00V~10.00V
0.00V
○
AI2 LOW
LIMIT
P5.21
AI2 lower limit
corresponding
setting
-100.0%~100.0%
0.0%
○
AI2 LOW
SETTING
P5.22
AI2 upper limit
0.00V~10.00V
5.00V
○
AI2 UP LIMIT
P5.23
AI2 upper limit
corresponding
setting
-100.0%~100.0%
100.0%
○
AI2 UP
SETTING
P5.24
AI2 filter time
constant
0.00s~10.00s
0.10s
○
AI2 FILTER
TIME
P5.25
AI3 lower limit
-10.00V ~10.00V
0.00V
○
AI3 LOW
LIMIT
P5.26
AI3 lower limit
corresponding
setting
-100.0%~100.0%
0.0%
○
AI3 LOW
SETTING
P5.27
AI3 upper limit
-10.00V ~10.00V
10.00V
○
AI3 UP LIMIT
P5.28
AI3 upper limit
corresponding
setting
-100.0%~100.0%
100.0%
○
AI3 UP
SETTING
P5.29
AI3 filter time
constant
0.00s~10.00s
0.10s
○
AI3 FILTER
TIME
P5.30
AI4 lower limit
0.00V~10.00V
0.00V
○
AI4 LOW
LIMIT
P5.31
AI4 lower limit
corresponding
setting
-100.0%~100.0%
0.0%
○
AI4 LOW
SETTING
P5.32
AI4 upper limit
0.00V~10.00V
10.00V
○
AI4 UP LIMIT
P5.33
AI4 upper limit
corresponding
setting
-100.0%~100.0%
100.0%
○
AI4 UP
SETTING
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...