Detailed Function Description
71
6.7 P6 Group -- Output Terminals
Function
Code
Name
Description
Setting
range
Factory
Setting
P6.00
HDO
selection
0: High-speed pulse output
1: ON-OFF output
0~1 0
0: High-speed pulse output: The maximum pulse frequency is 50.0 kHz. Please refer to
description of P6.09.
1: ON-OFF output: Please refer to description of P6.03.
Notice: The output of HDO terminal is multi-function ON-OFF output.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P6.01
Y1 output selection
Open-collector
output
0~31 1
P6.02
Y2 output selection
Open-collector
output
0~31 0
P6.03
HDO ON-OFF
output selection
Open-collector
output
0~31 0
P6.04
Relay 1 output
selection
Relay output
0~31
3
P6.05
Relay 2 output
selection
Relay output
0~31
0
P6.06
Relay 3 output
selection
Relay output
0~31
0
OC/Relay output functions are indicated in the following table:
Setting
Value
Function
Description
0
No output
Output terminal has no function.
1
Run forward
ON: During forward run.
2
Run reverse
ON: During reverse run.
3
Fault output
ON: Inverter is in fault status.
4
Motor overload
Please refer to description of PB.04~PB.06.
5
Inverter overload Please refer to description of PB.04~PB.06.
6
FDT reached
Please refer to description of P8.25, P8.26.
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...