Detailed Function Description
56
6.4 P3 Group--Vector Control
Function
Code
Name
Description
Setting
Range
Factory
Setting
P3.00
ASR proportional gain K
p
1
0~100 0~100 20
P3.01
ASR integral time K
i
1 0.01~10.00s 0.01~10.00 0.50s
P3.02
ASR switching point 1
0.00Hz~P3.05
0.00~P3.05
5.00Hz
P3.03
ASR proportional gain K
p
2
0~100 0~100 25
P3.04
ASR integral time K
i
2 0.01~10.00s 0.01~10.00 1.00s
P3.05
ASR switching point 2
P3.02~P0.07
P3.02~P0.07
10.00Hz
P3.00
~
P3.05 are only valid for vector control and torque control and invalid for V/F
control. Through P3.00
~
P3.05, user can set the proportional gain K
p
and integral time K
i
of speed regulator (ASR), so as to change the speed response characteristic. ASR's
structure is shown in following figure.
Figure 6.8 ASR diagram.
P3.00 and P3.01 only take effect when output frequency is less than P3.02. P3.03 and
P3.04 only take effect when output frequency is greater than P3.05. When output
frequency is between P3.02 and P3.05, K
p
and K
I
are proportional to the bias between
P3.02 and P3.05. For details, please refer to following figure.
Figure 6.9 PI parameter diagram.
Содержание CHV Series
Страница 2: ......
Страница 12: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverter 15kw and below...
Страница 13: ...Introduction 5 Figure 1 3 Parts of inverters 18 5KW and above...
Страница 23: ...Disassemble and Installation 15 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 25: ...Wiring 17 4 1 Connections of Peripheral Devices Figure 4 1 Connections of peripheral devices...