Chapter 4 Unit connection / In
stallation and Wiring
4.3 Wiring method
ME0394-1A
4-14
[DeviceNet]
Connector name
DeviceNet cable connector
Remarks
Cable side
MSTB2.5/5-STF-5.08 AU M (Phoenix Contact)
Standard
accessories
Controller side MSTBA2.5/5-GF-5.08 AU (Phoenix Contact)
Pin No.
Signal name
(color scheme)
Description
Compatible
wire diameter
1
V- (black)
Power supply cable - side
DeviceNet
dedicated
cable
2
CAN L (blue)
Signal data Low side
3
-
Digital ground
4
CAN H (white)
Signal data High side
5
V+ (red)
Power supply cable + side
Controller side
Connector top view
Shield
Blue (CAN L)
Black (V-)
White (CAN H)
Red (V+)
Master unit
Slave device
The communication power must be
supplied from the outside.
Grounding resistance: 100
Ω
or less
(Class D grounding construction)
121Ω
121Ω
V+
V-
V+
V-
V+
V-
Red
White
Black
Blue
Red
White
Black
Blue
Red
White
Black
Blue
At the terminal, a terminal
resistor needs to be connected.
Содержание Rec
Страница 2: ......
Страница 25: ...Actuator Coordinate System ME0394 1A Intro 17 4 Rotary type 330 degree rotation specification 0 330 ...
Страница 133: ...Parameter 6 1 Parameter list 6 1 6 2 Parameter Details 6 2 R E C Chapter 6 ...
Страница 155: ...Revision history ME0394 1A Post 1 Revision history Revision date Revised content 2020 02 First Edition ...
Страница 156: ......
Страница 157: ......
Страница 158: ......