Chapter 4 Unit connection / In
stallation and Wiring
4.3 Wiring method
ME0394-1A
4-12
4.3.5 Each field network wiring
For details of the connection method, follow the instruction manuals of the master unit of each
field network and the PLC configured.
[CC-Link]
Connector name
CC-Link cable connector
Remarks
Cable side
MSTB2.5/5-STF-5.08 AU (Phoenix Contact)
Standard
accessories
Controller side MSTB2.5/5-GF-5.08 AU (Phoenix Contact)
Pin No.
Signal name
(color scheme)
Description
Compatible
wire diameter
1
DA (blue)
Signal line A
CC-Link
dedicated
cable
2
DB (white)
Signal line B
3
DG (yellow)
Digital ground
4
SLD
Connects the shield of shielded cables
(5-pin FG and control power connector 1-pin FG connected internally)
5
FG
Frame ground
(4-pin SLD and control power connector 1-pin FG connected internally)
Controller side
Connector top view
Shield (SLD)
Yellow (DG)
White (DB)
Blue (DA)
REC
-CC-Link
Specification
Master
unit
SLD and FG are
internally connected.
At the terminal, a terminal resistor needs to
be connected.
The terminal resistor varies depending on
the type of CC-Link dedicated cable.
· Cable FANC-SBH: 130
Ω 1/2
W
(CC-Link dedicated high
performance cable)
· Cable FANC-SB: 110
Ω 1/2
W
(CC-Link dedicated cable)
Содержание Rec
Страница 2: ......
Страница 25: ...Actuator Coordinate System ME0394 1A Intro 17 4 Rotary type 330 degree rotation specification 0 330 ...
Страница 133: ...Parameter 6 1 Parameter list 6 1 6 2 Parameter Details 6 2 R E C Chapter 6 ...
Страница 155: ...Revision history ME0394 1A Post 1 Revision history Revision date Revised content 2020 02 First Edition ...
Страница 156: ......
Страница 157: ......
Страница 158: ......