Chapter 1 System Configuration and Specifications
1.5
Specifications
ME0394-1A
1-15
[Noise countermeasures and mounting method]
(1) Grounding for noise countermeasures (frame ground)
(2) Notes on wiring method
1) Have the 24V DC power supply wires twisted.
2) Separate the wiring of signal wires and encoders from power supply lines and power
lines.
(3) Noise sources and noise prevention
For the same power supply path and power supply
device in the same device, take measures against
noise.
Countermeasure examples for noise sources are
shown below.
1) AC solenoid valve / magnetic switch / relay
[Measure] Install an anti-noise device in parallel
with the coil.
2) DC solenoid valve / magnetic switch / relay
[Measure] Install a diode in parallel with the coil or
use the diode built-in type.
Annealed copper wire: 1.6 mm
diameter
Connect with a ground wire of
(2 mm
2
: AWG14)
Ground terminal
Grounding resistance: 100
Ω
or less
(Class D grounding construction)
Connect the ground wire to the
FG terminal block of the main
body.
Push in the square hole with a
screwdriver or the like to connect.
Controller
Controller
Grounding wires should not be connected
in common with other devices and
separate controllers should be grounded.
Anti-noise device
Relay
coil
Relay coil
Содержание Rec
Страница 2: ......
Страница 25: ...Actuator Coordinate System ME0394 1A Intro 17 4 Rotary type 330 degree rotation specification 0 330 ...
Страница 133: ...Parameter 6 1 Parameter list 6 1 6 2 Parameter Details 6 2 R E C Chapter 6 ...
Страница 155: ...Revision history ME0394 1A Post 1 Revision history Revision date Revised content 2020 02 First Edition ...
Страница 156: ......
Страница 157: ......
Страница 158: ......