Chapter
7 T
roubleshooting
7.3
Causes and countermeasures for ELECYLINDER alarms
7-6
ME0394-1A
7.3.2 Troubleshooting for alarm groups
ELECYLINDER alarms are classified into "alarms" and "warnings" depending on the content.
"Alarms" are grouped into 5 types.
Alarm
level
SV/ALM
LED
* ALM
signal
Situation
when
generated
Clearing method
Alarm
Red ON
OFF
Servo OFF
after gradual
stop
Cleared by resetting the alarm.
If it cannot be cleared by resetting the
alarm, turn off the power, then turn it on
again.
Warning
Red/green
alternate
blinking
ON
Continued
operation
●
Maintenance Warnings 1/2
(Total travel count/Total travel
distance) are cleared by updating the
set values in the maintenance
information window.
●
Maintenance Warning 3 (Overload
warning) is cleared by resetting the
alarm.
* ELECYLINDER should get into the motor voltage drop condition (Alarm displayed on teaching
pendant: 203)
if an emergency stop switch on a teaching pendant connected to the EC
gateway unit is pressed and held or the condition gets into the disable condition with the
deadman's switch.
Caution
●
Clear alarms only after investigating and resolving the cause.
●
If the same alarm recurs after clearance, it is highly probable that the cause of the alarm
has not been resolved.
●
If the cause of the alarm cannot be resolved or the alarm cannot be cleared after
resolving the cause, contact IAI.
Содержание Rec
Страница 2: ......
Страница 25: ...Actuator Coordinate System ME0394 1A Intro 17 4 Rotary type 330 degree rotation specification 0 330 ...
Страница 133: ...Parameter 6 1 Parameter list 6 1 6 2 Parameter Details 6 2 R E C Chapter 6 ...
Страница 155: ...Revision history ME0394 1A Post 1 Revision history Revision date Revised content 2020 02 First Edition ...
Страница 156: ......
Страница 157: ......
Страница 158: ......