Chapter 5 Operation
5.3 I/O Signals
5-23
ME0394-1A
The torque (current limit value) configured for [Pressing force] in the Simple Data Setting screen
judges completion of pressing operation.
When the ELECYLINDER is performing pressing operation, satisfying the following conditions
will produce a judgment of pressing complete, turning ON the PE signal.
(Accumulated time in which current has reached pressing value [%]) -
(Accumulated time in which current is less than pressing value [%]) ≥ 255ms
Points of caution for when the workpiece is not struck (no contact) and the movement to forward
end or backward end is complete. Consider a master device sequence or detection method
based on the content below.
●
If no contact is made, the PE signal will not turn ON.
A timer is required to determine if no contact has been made.
●
After a non-contact operation, the unit will stop in the pressing operation status.
●
If the workpiece shifts once pressing complete is determined and the PE signal is ON,
the ELECYLINDER will start another approach operation with the PE signal still ON. If the
workpiece cannot be pressed again, it will remain ON even with no contact.
Reference
Reference
Current
Time
Pressing [%]
Operation
start
Approach operation end
Pressing start
200ms
20ms
75ms
295ms
200ms + 75ms -
20ms ≥ 255ms
Pressing complete (PE output)
Contacting
workpiece
Decrease in current due to
movement of workpiece
Содержание Rec
Страница 2: ......
Страница 25: ...Actuator Coordinate System ME0394 1A Intro 17 4 Rotary type 330 degree rotation specification 0 330 ...
Страница 133: ...Parameter 6 1 Parameter list 6 1 6 2 Parameter Details 6 2 R E C Chapter 6 ...
Страница 155: ...Revision history ME0394 1A Post 1 Revision history Revision date Revised content 2020 02 First Edition ...
Страница 156: ......
Страница 157: ......
Страница 158: ......