Chapter 3 Operation
3.4 Field Network
Address Map
83
(ON = Applicable bit is “1”, OFF = Applicable bit is “0”)
Signal Type
Bit
Symbol
Description
Details
Current
Position
32 bits
–
32-bit signed integer indicating the current position
Unit: 0.01mm
(Example) If +10.23mm, input 000003FF
H
(1023mm in decimal system).
(Note) Negative numbers are two’s complement.
3.6 (21)
Completed
Position
No.
(Simple
Alarm
Code)
16 bits
PM1 to
PM256
16-bit integer
The positioning complete position number is output
in a binary number once getting into the positioning
width after moving to the target position.
In the case that the position movement has not
been performed at all, or during the movement, “0”
is output. Read it by turning PEND Signal ON after
movement.
The simple alarm code (refer to Chapter 5.
Troubleshooting) is output while an alarm is issued
(ALM of Status Signal is ON).
3.6 (21)
b15
EMGS
This signal turns ON during an emergency stop
3.6 (2)
b14
CRDY
This signal turns ON when the controller is
standing by.
3.6 (1)
b13
ZONE2
“ON” for the current position within the zone 2 set
range
The zone range setting is necessary for the
parameter.
b12
ZONE1
“ON” for the current position within the zone 1 set
range
The zone range setting is necessary for the
parameter.
3.6 (11)
b11
PZONE
Position zone (Invalid in Simple Direct Mode)
This signal turns ON when the current position is
inside the specified position zone.
3.6 (11)
b10
MODES
Teaching mode Signal
(Invalid in Simple Direct Mode)
This signal is ON while the teaching mode is
selected.
3.6 (15)
b9
WEND
Position data import complete
(Invalid in Simple Direct Mode)
This signal turns ON when writing is complete.
3.6 (16)
b8
b7
b6
–
Cannot be used.
–
b5
PSFL
“ON” for pressing and a miss
3.6 (20)
b4
SV
This signal turns ON when operation standby is
complete (Servo is ON).
3.6 (5)
b3
ALM
This signal is ON while an alarm is generated.
3.6 (3)
b2
MOVE
This signal is ON while in movement.
3.6 (8)
b1
HEND
This signal turns ON at home return complete and
is kept unless the home position is lost due to a
factor such as an alarm.
3.6 (6)
PLC Input
Control
Signal
b0
PEND
This signal turns ON at positioning complete and is
kept ON during a stop with the servo ON, but does
not turn ON when pressing operation is failed.
3.6 (9)
ME0302-4A
Содержание ERC3
Страница 1: ...IAI Corporation ERC3 Gateway Unit Instruction Manual Forth Edition ...
Страница 2: ......
Страница 4: ...ME0302 4A ...
Страница 8: ...ME0302 4A ...
Страница 35: ...Chapter 1 Specifications Check 1 6 Option 27 1 6 Option はケーブル長 ME0302 4A ...
Страница 54: ...Chapter 2 Wiring 2 3 Wiring Method 46 ME0302 4A ...
Страница 158: ...Chapter 3 Operation 3 8 Field Network LED Indication 150 ME0302 4A ...
Страница 160: ...Chapter 4 I O Parameter 152 ME0302 4A ...
Страница 176: ...Chapter 5 Troubleshooting 5 4 Alarm List 168 ME0302 4A ...
Страница 186: ......
Страница 187: ......