Chapter 3 Operation
3.6 I/O Signal Controls and Function
129
(21) Operation for Positioner 1/Simple Direct Modes
If the position data is written to the target position register (for Simple Direct Mode) or the target
position is set in the position data of ERC3 (for Positioner 1 Mode), the operation shall be made
with other information, such as the speed, acceleration/deceleration, pressing width, pressing
force, etc., set to the position data.
● Example of operation (Normal Positioning Operation with Simple Direct Mode)
(Preparation) Set the axis numbers to be used in Simple Direct Mode with Gateway Parameter
Setting Tool. [Refer to 3.2. Initial Setting.]
Set the position data items (speed, acceleration/deceleration, pressing width, etc)
except for the target position item, in the position table.
1) Set the target position data in the target position register.
2) Set the position No. where the speed and acceleration/deceleration, etc., have been set, in
the setup position No. register.
3) In the condition where the positioning completion (PEND) signal is turned “ON” or under
movement signal (MOVE) is turned “OFF”, turn “ON” the positioning command (CSTR)
signal.
The data items set in Steps 1) and 2) are read in the controller at the startup (ON edge) of
the CSTR signal.
4) After the CSTR signal is turned “ON”, the PEND signal is turned OFF after tdpf.
5) After confirming that the PEND signal is turned “OFF” or MOVE signal is turned “ON”, turn
“OFF” the CSTR signal. Do not change the value in the target position register until the
CSTR signal is turned “OFF”.
6) At the same time when the PEND signal is turned “OFF”, the MOVE signal is turned “ON”.
7) The current position data is continuously updated. When the remaining travel distance
becomes within the range of the positioning width set in the position data, and the CSTR
signal is turned “OFF”, the PEND signal is turned “ON”. Then, the completed position No. is
output to the completed position No. register.
Accordingly, for the read of the completed position No. register when the positioning is
completed, confirm it some time (Remaining Travel Distance Movement Time) after the
PEND signal is turned “ON”.
The current position data might be changed slightly even when the system is stopped.
8) MOVE signal turns OFF at the same time as or within 10ms after PEND signal turns ON.
9) The target position data can be changed during the actuator movement.
In order to change the target position, change the target position data and turn ON the
CSTR signal after the time longer than the PLC scanning time has passed.
Change the value for the CSTR signal after the time longer than the PLC scanning time has
passed.
● Example of operation (Pressing operation)
For the pressing operation, set the current limit to the pressing force box and pressing width to
the pressing width box in the position data at the stage of (preparation). By conducting a
positioning operation towards the set position number, the actuator performs a pressing
operation.
ME0302-4A
Содержание ERC3
Страница 1: ...IAI Corporation ERC3 Gateway Unit Instruction Manual Forth Edition ...
Страница 2: ......
Страница 4: ...ME0302 4A ...
Страница 8: ...ME0302 4A ...
Страница 35: ...Chapter 1 Specifications Check 1 6 Option 27 1 6 Option はケーブル長 ME0302 4A ...
Страница 54: ...Chapter 2 Wiring 2 3 Wiring Method 46 ME0302 4A ...
Страница 158: ...Chapter 3 Operation 3 8 Field Network LED Indication 150 ME0302 4A ...
Страница 160: ...Chapter 4 I O Parameter 152 ME0302 4A ...
Страница 176: ...Chapter 5 Troubleshooting 5 4 Alarm List 168 ME0302 4A ...
Страница 186: ......
Страница 187: ......