NO TE
Currently, the IVS1800 and NTP source server must be in the same LAN for NTP
synchronization. For details, see
.
If the IVS1800 and the NTP source server are not in the same LAN, you need to
manually set the time as follows: Choose Local Configuration > Server configuration
and change Timezone config and Time config based on the time of the source server
to be synchronized.
4. Choose Maintenance > Unified Configuration, set Module Name to MU,
and click Search.
5. In the search result, click Edit in the row where the value of Parameter Name
is MUNNatIP and set Value to the external IP address of the IVS1800. Click
Save.
Figure 6-27 Setting the external IP address of the MU
6. Click Edit in the row where Parameter Name is NatRtspServerPort and set
Value to 554. Click Save.
NO TE
– In the smart ETH gateway networking scenario, the external IP address set for
MUNNatIP is the same as the external IP address mapped for the IVS1800 on the
ECC800-Pro.
– If no external IP address is mapped, retain the default value of NatRtspServerPort.
7. Set Module Name to OMU and click Search.
8. In the search result, click Edit in the row where the value of Parameter Name
is OMUNNatIP and set Value to the MUNNatIP address of the MU. Click
Save.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
177