Step 8 Click
on the toolbar to save the device information.
Step 9 Click Connection test to start the connection test.
----End
6.5.7 Adding a PDU
6.5.7.1 Setting Monitoring Parameters for a PDU8000
Prerequisites
●
The IP address planned for the PDU8000 is obtained.
●
The PDU8000 is powered on.
NO TE
The Modbus TCP protocol is recommended for connecting the PDU8000 to the NetEco.
Context
Before connecting the PDU8000 to the NetEco over Modbus-RTU, set monitoring
parameters, such as Serial port baud rate and Serial port address.
Procedure
Step 1 Tap Settings on the PDU8000 home screen.
Step 2 Enter the PDU8000 user name and password and tap
.
NO TE
The preset user name and password for the PDU8000 are admin and 000001 respectively.
To ensure access security, change the password upon the first login.
Step 3 Click Communication.
Set Serial port baud rate and Serial port address.
Table 6-48 Parameter description
Parameter
Description
Serial port baud rate
Indicates the baud rate. The default
baud rate is 9600. Set BaudRate for
the collector port to the same value.
DataBit, StopBit, and Parity for the
PDU8000 cannot be set on the WebUI.
Their values are 8, 1, and None
respectively.