5. In the displayed SNMP Trap dialog box, set SNMP trap parameters, and click
Confirm.
–
Enter the IP address of the NetEco server in the Trap Target Address text
box.
–
Set Trap Port to 162.
Figure 8-1 Setting SNMP trap parameters
6. Click Confirm.
Step 4 Modify the UPS2000-G/UPS2000-H SNMP trap parameters (WebUI 2)
1. Log in to the UPS2000-G/UPS2000-H WebUI.
2. Choose Configure > SNMP.
3. In the NMS Address and Permissions Settings area, select the line where the
value of NMS addr. is the same as the NetEco IP address before change in the
No. column, and click Delete.
4. Click Add, enter the IP address of the NetEco server in the NMS addr. text
box, and click Add.
5. In the SNMP TRAP area, select the line where the value of Trap addr. is the
same as the NetEco IP address before change in the No. column, and click
Delete.
6. Click Add, enter the IP address of the NetEco server in the Trap addr. text
box, enter 162 in the Trap port text box, and click Add.
----End