4
Connecting Monitoring Cables to
Devices
NO TICE
Cable connections specified in this document are based on the cable connection
sequences specified in Preparing a Monitoring Cable. Connect cables in required
sequences by referring to Preparing a Monitoring Cable to prevent device
connection failures.
Unless otherwise specified, all network cables in this document are crossover
cables.
4.1 Scenarios for Connecting a Server
4.1.1 Server Ports
4.1.1.1 Server Ports (TaiShan 200 Server)
The TaiShan 200 server (Model 2280) is a next-generation data center server
developed by Huawei. Based on Huawei Kunpeng processors, the server features
efficient computing, high security and reliability, and an open ecosystem. As the
monitoring host of the NetEco management system, the server processes and
analyzes data.
Figure 4-1 Ports on the TaiShan 200 server (Model 2280)
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
4 Connecting Monitoring Cables to Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
67