For security purposes, you are advised to set Permission to Read.
–
Record the User Name, MD5/SHA Password, and DES/AES Password for
using when creating a UPS2000-G on the NetEco.
Figure 6-45 Setting SNMP parameters_03
5. Click Add in NMS Address and Permission Settings.
6. In the displayed Add NMS Address Info dialog box, set related parameters
and click Add.
–
Enter the IP address of the NetEco server in the NMS addr. text box.
–
For security purposes, you are advised to set Permission to Read.
Figure 6-46 Adding the NMS IP address
7. Click Add under SNMP TRAP.
8. In the displayed Add SNMP Trap dialog box, set related parameters and click
Add.
–
Enter the IP address of the NetEco server in the Trap Address text box.
–
Set Trap port to 162.
----End