Table 6-30 NetEco parameters
Path
Parameter
Default
Value
Setting
System
Settings >
NMS
Application
> NetEco >
Communicat
ion
Parameters
Server IP
192.168.8.
11
IP address of the primary NetEco
server
NOTE
The NetEco IP address and the ECC800-
Pro IP address must be configured in
the same network to ensure normal
connection between the NetEco and
the ECC800-Pro.
Port number
31220
31220
Network port
for link setup
WAN_1
WAN_1
Table 6-31 Setting an authentication password
Path
Parameter
Default
Value
Setting
System
Settings >
NMS
Application
> NetEco >
Set
Authenticati
on Password
Authenticatio
n password
Modifyme
_123
Set this parameter based on
customer requirements.
NOTE
Requirements for setting passwords:
'a~z','A~Z','0~9','~!@#^*_={}:,./?-`
$'(8-32 characters that include at least
three of the following types: lowercase
letters, uppercase letters, digits, and
special characters)
Confirm
authenticatio
n password
-
-
Step 4 Click Submit.
----End
6.5.1.6 Creating an ECC800-Pro Collector on the NetEco
This section describes how to create an ECC800-Pro collector on the NetEco.
Prerequisites
●
You have created a smart module or container in Planning Configuration.
●
The IP address of the NetEco connected has been configured on the ECC800-
Pro WebUI.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
234