Related Tasks
●
Exporting configuration parameters
Choose Export > Configuration Parameters, export the configuration
parameter form, and modify configuration parameters.
Figure 6-10 Exporting configuration parameters
●
Exporting algorithm parameters
Choose Export > Algorithm Parameters, and export the algorithm parameter
form.
6.2.3.3 Viewing iCooling Energy Efficiency on the NetEco
On the overview page, you can view the PUE, accumulated energy consumption,
and running overview of the data center. After the iCooling function is enabled,
the system displays the running information in energy saving mode.
Prerequisites
●
You have created a management domain on the Planning Configuration
page.
●
You have added the ChillerPlantControl device to the management domain.
●
You have installed the iCooling energy efficiency management license and
obtained the iCooling energy efficiency management permission.
●
You have configured power and cooling capacity counters on the PUE
Configuration page. For details, see "Configuring PUE Counters" in
iMaster
NetEco Product Documentation (DC) (V600R021C10_xx)
.
Procedure
Step 1 Log in to the NetEco client.
Step 2 Choose Energy Efficiency Management > Energy Saving Management >
iCooling.
Step 3 Select the required management domain from the drop-down list in the upper-
right corner of the page.
Step 4 View Overall Running Status, PUE(Hours), Energy Saving and Total Consumed
Energy, and Running Overview.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
154