2. Set IP address, Subnet mask, and Gateway as planned.
3. Tap SNMP Configuration to enter the setting screen.
Figure 6-58 SNMP Configuration
4. On the SNMP Configuration screen, set SNMP Version to SNMPv3, retain
the default value 161 for SNMP Port, and tap Submit.
5. Tap Add under SNMPv3 User. Set User Name. Set Auth. protocol to SHA,
and specify MD5/SHA and Confirm Password. Set Private protocol to AES,
and specify DES/AES and Confirm Password. After setting the parameters,
tap
.
6. Select Privacy protocol to AES, specify DES/AES and Confirm Password, and
tap
.
7. On the Trap Config. screen, tap Add, set Trap Des. Address to the IP address
of the NetEco server and set Trap Port to 162. Select SNMP Version to
SNMPv3. After setting the parameters, tap
.
----End
6.4.6.2 Setting PDU8000 Monitoring Parameters (Modbus TCP)
Prerequisites
●
You have obtained the IP address, subnet mask, and default gateway planned
for the PDU8000.
●
The PDU8000 is powered on.
Context
Before connecting the PDU8000 to the NetEco, set monitoring parameters such as
the IP address on the PDU8000.
Procedure
Step 1 Tap Settings on the PDU8000 home screen.
Step 2 Enter the PDU8000 user name and password and tap
.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
214