Parameter
Description
Port
Set this parameter to the port number of the device.
NOTE
When creating a smart cooling product of the Modbus-TCP type, if the
smart cooling product functions as a server, set the port number to 502.
If the smart cooling product functions as a client, set the port number to
1. If the smart cooling product functions as a server and a client, set the
port number to 502 or 1.
Device
Address
Set this parameter to the address set on the device.
Connection
Mode
Indicates the connection mode of a device. You can set this
parameter to Non-SSL Connection or SSL Connection.
If you modify Connection Mode on the NetEco, you must
modify Connection Mode on the WebUI of the device at the
same time.
NOTE
● Connection Mode for the NetEco and device must be the same.
● By default, Connection Mode is set to SSL Connection for the
NetEco and device.
● A non-SSL connection has security risks. You are advised to select the
secure SSL connection.
Authenticatio
n Password
Indicates the re-authentication password for the NetEco and
device.
1. Click Modify.
NOTE
After the device is saved, the Modify button is displayed.
2. In the displayed dialog box, enter the New Password and
Confirm Password.
NOTE
– The default re-authentication password for the NetEco and device
is Modifyme_123.
– The device password should be consistent with the NetEco
password.
– If the password does not meet requirements, modify it on the
device.
3. Select Send To Device.
NOTE
If you select YES, the re-authentication password for the NetEco and
device is changed at the same time. If you select NO, only the re-
authentication password of NetEco is changed on the server.
4. Click OK.
Timeout
Period
Timeout duration for a connection test. The default value is 3s.
Step 8 Click
on the toolbar to save the device information.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
192