Figure 6-28 Setting the external IP address of the OMU
Step 5 Enable camera NTP synchronization.
The camera NTP synchronization function for the server is disabled by default. The
camera NTP synchronization function needs to be enabled for the server that
connects to the camera. After the camera NTP synchronization function is enabled,
cameras will automatically time-synchronize from their access servers.
1. Log in to the OMU portal as the admin user.
2. Choose Maintenance > Unified Configuration.
3. Set Module Name to SCU and Parameter type to System property, and
click Search.
4. In the search results, click Edit in the row where Parameter Name is NTPIPC
and set Value to 1.
5. Click Save. After the camera NTP synchronization function is enabled, the
camera, after being connected to the server, will automatically time-
synchronize with the server.
Figure 6-29 Configuring camera NTP synchronization
Step 6 Create a user.
When connecting to the IVS1800 on the NetEco, you need to log in to the VCN as
a non-admin user.
1. Log in to the OMU portal as the admin user.
2. Choose User Management > Add User.
NO TE
When creating a user, you can select Enable account validity period and set Valid from
and Valid to to set the account validity period for the created user.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
178