FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
3 Hardware Installation
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
53
Figure 3-27
Oil trap (unit: mm)
Gas Pipe, Liquid Pipe, and Thermal Insulation Foam (Optional)
lists the specifications for pipes and thermal insulation foam.
Table 3-2
Specifications
Item
Specifications
Gas pipe
5/8 inch (15.88 mm), wall thickness: 1.0 mm;
pressure withstanding capacity ≥ 4.5 MPa
Liquid pipe
3/8 inch (9.52 mm), wall thickness: 0.75 mm;
pressure withstanding capacity ≥ 4.5 MPa
Thermal insulation foam
≥ 13 mm
Water pipe