FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
3 Hardware Installation
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
167
Figure 3-191
Installing an AI/DI module
Step 3
Set the address for the AI/DI module to 1.
Figure 3-192
Setting an address
----End
3.11.11 Connecting a Cable to the WLDS900 Water Sensor
Context
The water sensor is composed of the water detection cable (BOM number: 33010445),
water detector (BOM number: 33010352), and conversion cable (packed with the water
detector).
The water detector is installed in the Converged Cabinet, as shown by (2) in
The water detection cable and water detector are interconnected using the conversion
cable.
shows the connections of the components and cables.
A single water detection cable is 5 meters long. If a longer cable is required, connect the
male connector of a water detection cable to the female connector of another. One water
detector can be connected to a maximum of nine water detection cables.