6 Power-On Commissioning
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
247
Running Parameters
, and set
Logical level configuration for reader removed
of the
corresponding card reader to
High level alarm
.
Table 6-10
Setting method
Cable Connection Scenario
Setting Method
The card reader with a keypad is
connected to WG_1 port on the access
actuator.
Set
Logical level configuration for reader 1
removed
to
High level alarm
.
Logical level
configuration for reader 2 removed
remains as
Low level alarm
.
The card reader with a keypad is
connected to WG_2 port on the access
actuator.
Set
Logical level configuration for reader 2
removed
to
High level alarm
.
Logical level
configuration for reader 1 removed
remains as
Low level alarm
.
If the access control system uses a
Card
,
Card and fingerprint
, or
Card, password
and fingerprint
reader, retain the default value
Low level alarm
for
Logical level
configuration for reader removed
.
Step 3
Check the functions of the access control device and access actuator.
Table 6-11
Function check
Check Method
Normal Connection Status
Method 1: Attempt to open the door using
the configured authentication mode.
NOTE
For example, if you select
Card, password and
fingerprint
for the authorization mode, the door
can be opened only after you swipe an authorized
card first, enter the authorized password (press #
to confirm the password), and then scan the
fingerprint.
Method 2: On the WebUI, choose
Monitoring
>
Aisle
>
Access Actuator
Group
>
Access Actuator n
, and click
Controls
to open the door remotely.
For method 1: The aisle door is opened
successfully.
For method 2: After you choose
Query
>
Access Event
on the WebUI, you can view
the type of this access control event.
----End
6.3.6.6 (Optional) Commissioning an In-Room Exit Button
Procedure
Step 1
Check functions of the exit button.