6 Power-On Commissioning
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
267
Figure 6-23
T/H sensor layout and DIP switch address (3 cabinets and 1 smart cooling product)
----End
6.4.2.2 Setting Teamwork Control Parameters
Context
Teamwork control parameters have the following bidirectional coupling relationships:
Number of running units ≤ Total number of units
Teamwork group no.: Group the smart cooling products in adjacent areas as one, that is,
assign one teamwork control number for them. At most four teamwork control groups
can be assigned (1–4).
Teamwork unit address: The addresses for the smart cooling products in the same group
cannot be the same (address range 1–32). The smart cooling product addressed 1 is the
master one that collects, processes, and delivers data. You are advised to set the value to
an integer in the range of 1 to the number of smart cooling products in the current group.
Procedure
Step 1
Log in to the ECC800 WebUI as admin.
Step 2
Choose
Monitoring
>
Air Conditioner
>
NetCol5000-A0101
>
Running Parameters
>
Teamwork Settings
to display the page for teamwork setting.
0101 in
NetCol5000-A0101
is variable and subject to change with the smart cooling product connection
sequence. The displayed value prevails.
Step 3
Set teamwork control parameters.