6 Power-On Commissioning
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
248
Table 6-12
Function check
Check That
Normal Connection Status
Open the door by pressing the exit button
when the aisle door is properly closed.
The room door is opened properly.
----End
6.3.6.7 (Optional) Commissioning an In-Room Emergency Door Release
Button
Procedure
Step 1
Check the function of an emergency door release button.
Table 6-13
Function check
Check That
Normal Connection
Status
Follow-up Procedure
When the room door is
properly closed, short circuit
the wiring terminals NO and
COM on the emergency
door release button.
The room door is opened
properly.
Remove the short-circuit
cable on the emergency door
release button.
----End
6.3.7 Setting iBOX and iBAT Parameters
Procedure
Step 1
Log in to the ECC800 WebUI as an administrator.
Step 2
Choose
Monitoring
>
Power Distribution
>
iBOX/CIM
>
Running Parameters
.
Step 3
Click
Unhide All Advanced Signals
, set
iBOX single battery qty.
,
Batt. installation time
,
Single battery capacity
,
Current source
, and
Battery string No.
. Retain default values for
other parameters.
Table 6-14
Setting iBOX parameters
Parameter
Description
Remarks
iBOX/CIM single
battery qty.
Total number of batteries monitored by
the iBOX/CIM
Set this parameter based
on the battery parameter
planned by the customer.
Batt installation
Actual time at which batteries are
-