FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
A Appendix
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
286
Figure A-11
Connecting the dehumidifier drainpipe
(1) Smart cooling product drainpipe in the
equipment room
(2) Three-way
valve
(3) PVC pipe
(4) Female adapter
(5) Male plug
(6) Dehumidifier
drainpipe
4.
Apply PVC glue where the three-way valve, PVC pipe, female adapter, and the cut smart
cooling product drainpipe are connected.
Precautions for PVC pipe connection:
Clear burs from the PVC pipe port chamfer the pipe port, and clean dust, water, or oil from
the pipe port using a piece of dry cloth.
Apply PVC glue evenly on the surface of the socket using a brush.
Align the two pipes to be interconnected, quickly insert the plug port into the socket port,
turn the plug port by one fourth circle, and keep the pipes stable for 10 minutes to enable
the PVC glue to consolidate and get evenly distributed.
Wipe off redundant PVC glue on the pipe surface using a piece of cloth, and switch on the
water supply 2 hours later.
5.
Wrap thermal insulation foam around the pipe.
6.
Apply sealing tape to the threads where the female adapter and male plug are connected
to seal them up.
7.
Cut through the male plug using a handsaw, and insert the dehumidifier drainpipe into
the plug by at least 50 mm.
8.
Apply AB glue evenly where the dehumidifier drainpipe and the male plug are
connected, and keep the glued parts steady for 30 minutes to solidify the glue.