Application
Scenario
Specifications
Remarks
(optional)
Naked crimping terminal, single-wire cord
end terminal, 1.5 mm
2
, 7.5 A, tin plating,
insertion depth 12 mm, black
Delivered with the
fittings
Naked crimping terminal: OT, 1.5 mm
2
, M4,
18 A, tin plating, 22-16 AWG, red
Delivered with the
fittings
3.7.2 Installation Layout
The layout principles are as follows:
If the outdoor unit is placed higher than the indoor unit, the maximum height deviation
between them should be less than or equal to 20 meters. Install an oil trap every 5–6
meters in the vertical direction along the gas pipe.
If the indoor unit is placed higher than the outdoor unit, the maximum height deviation
between them should be less than or equal to 5 meters.