FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
6 Power-On Commissioning
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
271
Remove the refrigerant cylinder after ensuring that no refrigerant is required.
Users are categorized as admin (preset password:
Changeme
) and operator (preset
password:
Changeme
). To enter the diagnostic mode, log in as admin.
If the smart cooling product is not configured with a heater or humidifier, skip the
commissioning steps related to the electric heater and wet film humidifier.
The electric heater and humidifier can not work at the same time.
Procedure
Step 1
Log in to the ECC800 WebUI as admin. Choose
Monitoring
>
Air Conditioner
>
NetCol5000-A0101
to display the smart cooling product commissioning page.
0101
in
NetCol5000-A0101
is variable and subject to change with the smart cooling product
connection sequence. The displayed value prevails.
If no manual operation is performed within 25 seconds after you click
On
, the device will
automatically run following the preset logic, and the compressor and indoor and outdoor fans will
also run according to the environment.
Step 2
Choose
Controls
>
Control Information
, set
On/off status on EMS
to
On
, and then click
Submit
.
Step 3
Choose
Controls
>
Control Information
, set
Diagnostic mode
to
Enable
, and then click
Submit
.
Step 4
(Optional) Choose
Running Parameters
>
Diagnostic Mode Parameters
, set
Elec heater
manual control
to
Open
, and then click
Submit
.
1.
Check that the indoor fan operates properly, without alarms.
2.
If hot air blows out from the air exhaust vent of the fan after a period of time, the electric
heater runs properly. Set
Elec heater manual control
to
Off
and click
Submit
.
Step 5
(Optional) Commission the wet film humidifier.
1.
On the
Diagnostic Mode Parameters
page, set
Inlet solenoid man ctrl
to
Open
and
click
Submit
. Check that the water inlet pipe does not leak and the humidifier float
works properly. Set
Inlet solenoid man ctrl
to
Closed
and click
Submit
.
2.
On the
Diagnostic Mode Parameters
page, set
Humidifier film man ctrl
to
Open
and
click
Submit
. Choose
Running Info
>
Humidifier Information
>
Humidifier pump
ctrl
to check that the humidifier water pump is
Open
in normal status and water flows
down along the wet film. Set
Humidifier film man ctrl
to
Closed
and click
Submit
.
Step 6
Commission the condensate pump.
1.
Lift the low liquid level detector. After 5 seconds, you will hear the water pump
operating sound.
2.
Lay down the low liquid level detector.
It is normal if a condensate pump faulty alarm is generated during the pump operation when there is no
water in the pan. The condensate pump generates this alarm for self-protection. The alarm needs to be
cleared manually.