FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
3 Hardware Installation
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
100
Applicable
Scenario
No.
Cable
Name
From
To
Cable
Specifications
Remarks
the IT cabinet to
the PDC in the
converged cabinet
along the smart
cooling product
pipes.
2
Smart
cooling
product
control unit
input power
cable
Converged
cabinet
XT4-4
INPUT1 port on
the smart
cooling product
control unit
2 x 1.5 mm
2
Connected onsite
Route cables from
the IT cabinet to
the PDC in the
converged cabinet
along the smart
cooling product
pipes.
3
Outdoor
unit power
cable
L
(converged
cabinet
XT4-1,
XT4-2, and
XT4-3
correspond
to outdoor
units 3, 2,
and 1,
respectively
.), N bar,
PE bar
L, N, and
ground ports on
the electric
control box of
the outdoor unit
3 x 6 mm
2
Connected onsite
4
Signal
cables for
the indoor
and outdoor
units
X2.1, X2.2,
and X2.3
ports on the
indoor unit
P, Q, and E
ports on the
electric control
box of the
outdoor unit
3 x 16 AWG,
with the shield
layer that can be
grounded
Connected onsite
5
J1 cable
X101,
X102, and
X103 ports
on the
indoor unit
J1 port on the
smart cooling
product control
unit
N/A
Connected onsite
6
J2 cable
X101,
X102, and
X103 ports
on the
indoor unit
J2 port on the
smart cooling
product control
unit
N/A
Connected onsite
7
Smart
cooling
product
control unit
output
X1.1, X1.2,
X1.3, and
FU1-FU3
ports on the
indoor unit
OUT1 port on
the smart
cooling product
control unit
N/A
Connected onsite