2–46
edge switch 2/24 service manual
Diagnostics
5
Ensure the switch reporting the problem is connected to facility AC power. Inspect the
switch for indications of being powered on, such as:
•
At the front bezel, an illuminated power LED (green) or system error LED
(amber).
•
Audio emanations and airflow from cooling fans.
Does the switch appear powered on?
YES
NO
↓
A power distribution problem is indicated. Go to
MAP 0100: Power Distribution
Analysis on page 2-27
. Exit MAP.
6
At the switch, inspect the amber for the switch.
Is the amber LED illuminated?
NO
YES
↓
Failure of the CTP is indicated. Go to
MAP 0500: FRU Failure Analysis on
page 2-59
. Exit MAP.
7
The switch-to-server Ethernet link failed. Double-click the icon with the grey square
representing the switch reporting the problem. The Hardware View displays. At the
Hardware View:
•
A grey square appears at the alert panel.
•
No FRUs are visible for the switch.
•
The Edge-24 Status table is yellow, the Status field displays
No Link
, and the
Reason field displays an error message.
Table 2–8
lists the error messages and associated steps that describe fault isolation
procedures.
Table 2–8: MAP 400: Error Messages
Error Message
Action
Never connected.
Go to
step 8
.
Link timeout.
Go to
step 8
.
Protocol mismatch.
Go to
step 15
.