4–4
edge switch 2/24 service manual
FRU Removal and Replacement
b.
Clean the jumper cable and transceiver connectors. Refer to
Clean Fiber-Optic
Components on page 3–27
for instructions.
c.
Insert the keyed LC cable connector into the port’s optical transceiver.
5. Ensure the amber LED adjacent to the port transceiver is extinguished. If the
amber LEDs is illuminated, go to
MAP 0000: Start MAP on page 2–6
to isolate
the problem.
6. Perform one of the following to inspect the Event Log:
— If at a web browser connected to the EWS interface, click the Log tab at the
Monitor panel. The Event Log displays. Ensure an event code 510 (SFP
optics hot-insertion initiated) appears. If the event code does not appear in the
log, go to
MAP 0000: Start MAP on page 2–6
to isolate the problem.
— If at the HAFM server, open the Hardware View, click Logs, and select
Event Log. The Event Log displays. Ensure an event code 510 (SFP optics
hot-insertion initiated) appears. If the event code does not appear in the log,
go to
MAP 0000: Start MAP on page 2–6
to isolate the problem.
7. Perform one of the following to verify port operation:
If at a web browser connected to the EWS interface, open the Switch tab at the
View panel and:
a.
Ensure no amber LEDs illuminate that indicate a port failure.
b.
Click the graphic representing the port with the replacement transceiver to
open the Port Properties tab. Verify port and port technology information is
correct.
c.
If a problem is indicated, go to
MAP 0000: Start MAP on page 2–6
to isolate
the problem.
If at the HAFM server, open the Hardware View and:
a.
Ensure no alert symbols appear that indicate a port failure (yellow triangle or
red diamond).
b.
Double-click the graphic representing the port with the replacement
transceiver to open the Port Properties dialog box. Verify port information is
correct.