Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
90
9.3
Fire mode (Control panel: Menu PAR
P18)
Drive ignores all commands from keypad, fieldbus and PC tool and preset
frequency when activated. If activated, alarm sign is shown on the keypad
and warranty is void.
In order to enable the function, you need to set a password in the descrip-
tion field for parameter Fire Mode password. Please note, the NC (normally
closed) type of this input!
NOTE:
THE WARRANTY IS VOID IF THIS FUNCTION IS ACTIVATED!
There is also a different password for test mode to be used for
testing the Fire Mode without warranty becoming void.
Table 38. Fire mode.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P18.1
Fire mode password
0
9999
0
1599
1234
= Test mode
1001
= Enable
1515
= Disable
P18.2
Fire mode frequency select
0
Varies
0
1617
0
= Fire mode preset
1
= Preset speed 0
2
= Keypad
3
= Fieldbus
4
= AI1
5
= AI2
6
= PID
7
= AI+AI2
8
= Motor potentiometer
9
= AIE1
10
= Temperature input 1
11
= Temperature input 2
12
= Temperature input 3
NOTE!
This parameter will be locked when password for
fire mode is activated (not in the test mode), and not
only when fire mode input is set. To change the
parameter you have to disable fire mode.
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...